It realizes one-48V DC input and 10-48V DC output to supply power to BBU, RRU and other equipment.
Input current
1. Input capability 1*80A or 2*80A.
2. 1 * 80A input power line has a diameter of 16 mm ^ 2.
3. 2 * 80A input power line diameter is 2 16 mm ^ 2 power line.
Distribution Specification
10*30A (6 large fast plug terminals + 4 small fast plug terminals)
Size (width * height * depth)
442mm*42mm*65mm
lightning protection
Differential/Common Mode: 10KA/20KA
weight
1.65kg
Typical usage scenarios
BBU indoor placement, DC power supply scene. DCDU-12B can supply concentrated power to BBU and RRU.
DCDU-12B provides 10 channels open, using 10 fast plug-in terminals to support on-site wiring. Six large fast sockets support 2.5-10 square power lines, and four small fast sockets support 2.5-4 square power lines.
DCDU-12B supports 1 * BBU + 6 * RRU + 1 * FAN or 4BBU + 1 * FAN power supply. More than three RRUs require 2 routes and 16 inputs. See Appendix 1 for details.
The following points should be paid attention to when two open parallel circuits supply the same DCDU-12B power:
- Two open channels must be output by the same power supply system.
- The specifications of the two openings must be exactly the same (including the size and model of the openings).
- The specifications of the two input power lines must be exactly the same (including the length and diameter of the power lines, etc.).